|
(Continued from page 224)
(see Section IV-E). B. Faulty Meter B-1. Disconnect the red wire from red terminal B of the fuse block and connect a 0-50 amp DC ammeter between the red wire and red terminal B. Record the amperage reading during the treatment cycle. Compare with the treatment meter reading. Use Figure 8 at the end of this section to determine amperage on treatment meter. If amperage readings do not correlate (= or - 2 amps) the meter is defective. Replace meter.
Zero Meter Reading (Treatment Light Operates) A. Fuse B blown A-1. Replace fuse B. Be sure to check fuse specifications given in parts list on page 38. A-2. Check to see that connections on fuse clip are clean. Dirt and corrosion cause heat buildup which can result in a blown fuse. A-3. If replacement fuse blows in the next operating cycle, or soon after, the electrodes must be inspected for a short between the plates. The short can be caused by impingement of a conductive foreign body such as a bobby pin lodged between the plates. Remove the foreign object. A-4. Fuse B can also blow if the salt concentration in the flush water is excessive. Replace fuse, close valve on salt feed tank, and flush head 3 or 4 times without activating treatment cycle. This will dilute the salt concentration.
Zero Meter Reading (Treatment Light Operates) A. Fuse B blown A-1. Check meter reading during treatment cycle if meter reading registers in the High range, salt concentration is excessive. Adjust salt concentration. Close salt feed valve Flush toilet for a short period and then run operating cycle. Check meter reading. Repeat until meter reading is in Normal range. Readjust salt feed valve. (see Section IV)
B. Faulty Electrode Pack B-1. Disconnect the red wire from red terminal B of the fuse block and connect a 0-50 amp DC ammeter between the red wire and red terminal B. If there is no amperage and the salt concentration is at the proper level, then the electrode pack is defective. Replace electrode pack B-2. During treatment cycle check for proper voltage and amperage across electrode pack terminals C. Faulty Meter C-l. If there is proper voltage and amperage and meter does not register in treatment cycle, it is defective. Replace meter.
Zero Meter Reading (Treatment Light Inoperative) A. Blown Fuses A-1. Check fuses B and C. Replace if blown. See Treatment Light inoperative for fuse C and Zero Meter Reading. (Treatment Light Operates) for fuse B. B. Defective Timer B-1. Check for proper voltage (12, 24, or 32 VDC) to timer with a voltmeter, between terminal T-2 on the timer and terminal D on the relay. If there is no voltage, see System inoperative. B-2. If there is proper voltage, check timer operation. Check for proper voltage (12, 24, or 32 VDC) between terminal L-2 on the timer and terminal D on the relay during the flush/pretreat cycle. If there is no voltage, the timer is defective. Replace timer. B-3. Check for proper voltage (12, 24, or 32 VDC) between terminal T-3 on the timer and terminal D on the relay during the treatment cycle. If there is no voltage, timer is defective. Replace timer.
C. Defective Relay C-l. Check for proper voltage (12, 24, or 32 VDC) between terminals D and G on the relay during a treatment cycle. If there is no voltage, check all connections and re-check timer. C-2. Check for proper voltage (12, 24, or 32 VDC) between terminals D and F on the relay during the treatment cycle. If there is no voltage relay is defective. Replace relay. If there is proper voltage, recheck all electrical connections.
Toilet Does Not Flush A. Salt Feed Tank Empty A-1. Refill salt feed tank (Section V-E) A-2. If small end of spring of the check valve is toward metering plug, reverse the spring "end for end" and slip the large end of spring over the large boss on metering plug, to reduce tension.
VII. Preventive Maintenance
To assure continued trouble-free performance of the LECTRA/ SAN System, a number of routine preventive maintenance procedures should be performed periodically. The following table lists the parts to be checked, the recommended frequency of maintenance, and the maintenance procedures to be taken.
Salt Feed Tank, Monthly 1. Thoroughly rinse and wipe out tank. 2. Check to make sure the tiny vent hole In tank cap is not blocked. 3. Rinse out control valve with fresh water. Salt Feed Line, Every two months 1. Remove tubing from salt feed tank and from toilet, and remove metering plug. Check all parts for obstructions. 2. Wash out tubing, siphon check valve, and metering plug with fresh water. Treatment Unit, Every two months 1. Check to see that cover hold down bolts are properly tightened. 2. Clean cover motors and electrical contacts. 3. Check to see that terminal contacts are properly tightened. Control Unit, Every two months 1. Inspect and clean electrical connections. Hose Fittings, Every two months 1. Inspect all hose fittings and check for tight hose clamps. (Continued on page 226)
|
|