|
C. Defective Timer C-l. Check for proper voltage (12, 24, or 32 VDC) to the timer with a voltmeter between terminal T-2 on the timer and terminal D on the relay. If there is no voltage, see System Inoperative. C-2. If there is proper voltage, check timer operation Check for proper voltage (12, 24, or 32 VDC) between terminal L-2 on the timer and terminal D on the relay during the flush/pretreat cycle. If there is no voltage, timer is defective. Replace timer. C-3. Check terminal a on LED for tightness.
Treatment Light Inoperative A. Fuse C blown A-1. Replace fuse C. Be sure to check fuse specifications given in parts list on page 38. A-2. Check to see that connections on fuse clip are clean. Dirt and corrosion cause heat buildup which can result in a blown fuse. A-3. If replacement fuse blows in the next operating cycle or soon after, then the macerator (larger) motor must be inspected for damage or excess loading on the shaft. Replace defective motor or clean shaft and impeller.
NOTE: See Specification Section for proper amperages A-4. Check terminal c on LED for tightness. B. Defective LED Board B-1. Check for proper voltage (l2, 24, or 32 VDC) between terminals (c) and (d) on the LED Board during the treatment cycle. If there is proper voltage and the treatment light does not operate, then the LED Board is defective. Replace LED Board. B-2. If the proper voltage does not register between terminals (c) and (d) on the LED Board, check fuse C. (See A above ) If fuse C is good, check timer. C. Defective Timer C-1. Check for proper voltage (12, 24, or 32 VDC) to the timer with a voltmeter between terminal T-2 on the timer and terminal D on the relay, if there is no voltage, see System Inoperative. C-2. If there is proper voltage, check timer operation. Check for proper voltage (12, 24, or 32 VDC) between terminal L-2 on the timer and terminal D on the relay during the flush/pretreat cycle. If there is no voltage, timer a defective. Replace timer. C-3. Check for proper voltage (12, 24, or 32 VDC) between terminal T-3 on the timer and terminal D on the relay during the treatment cycle. If there is no voltage, timer is defective. Replace timer. C-4. Check terminal D for tightness. D. Defective Relay D-1. Check for proper voltage (12, 24, or 32 VDC) between terminals D and G on the relay during a treatment cycle. If there is no voltage, check all connections and recheck timer. D-2. Check for proper voltage (l2, 24, or 32 VDC) between terminals D and F on the relay, during the treatment cycle. If there is no voltage, relay is defective. Replace relay if there is proper voltage. Recheck all electrical connections.
LOW Meter Reading A. Insufficient Salt A-1. Check salt feed tank supply Refill if needed (Section V-E) A-2. Check for restrictions in salt feed line. A-3. Open valve on salt feed tank. A-4. Inspect siphon check valve (Item 5, Fig 11) for proper orientation. Be sure it is free of dirt or foreign materials. Clean in fresh water. A-5. Inspect T-Check Valve (Item 7. Fig 11) or metering plug (item 8, Fig. 11) if Raritan Crown Head being used. Check for restrictions. Clean in fresh water.
B. Low Voltage B-1. Check voltage with voltmeter between electrode studs on Treatment Unit during treatment cycle. Low voltage is less than 11.5 VDC (23 VDC for Model 24 VDC and 31 VDC for Model 32 VDC). If voltage is low, go to B-2. below. If there is proper voltage go on to C and D, below. B-2. Check voltage to the Control Unit between lugs D and E on the relay (see Fig 6) during the treatment cycle. Low voltage is less than 12 VDC (24 VDC for Model 24 VDC and 32 VDC for Model 32 VDC). If the proper voltage does not register, check main power wiring for proper size. Check connections if there is proper voltage, recheck wiring and connections between Control Unit and Treatment Unit. B-3. Check for fully charged battery.
C. Fouled Electrodes C-l. Inspect and clean electrodes (see Section VII).
D. Faulty Meter D-l. Disconnect the red wire from red terminal B of the fuse block and connect a 0-50 amp DC ammeter between the red wire and red terminal B Record the amperage reading during the treatment cycle. Compare with treatment meter reading. Use Figure 8 at the end of this section to determine amperage on treatment meter. If amperage readings do not correlate (= or - 2 amps), the meter is defective. Replace meter.
E. Electrode defective E-l. During treatment cycle, check amperage across electrode terminals (1/4" studs in center of treatment tank) E-2. During treatment cycle, check voltage across electrode terminals. E-3. Check battery voltage at battery during treatment cycle. There should be no more than 1 volt difference between the battery voltage and treatment tank terminal voltage. If voltage drop is greater, undersized wiring or a poor connection is indicated.
NOTE: Check Specification Section for proper electrode amperage.
F. Motor(s) Inoperative F-l. Check operation of mixer (smaller) motor during flush/pretreat cycle. Check operation of macerator (larger) motor during treatment cycle. Replace defective motor(s).
High Meter Reading A. Excess Salt A-1. Close off salt feed valve slightly
(Continued on page 225)
|
|