|
(Continued from page 222)
NOTE: Note the position of the indicator needle on the Control Unit meter during the treatment cycle, if it is not registering in the Normal range (and the salt feed tank is not empty) make the adjustment shown at the top of page 20, if the meter reading tends in time to drift to the Low range, refer to Section VI. Troubleshooting, for corrective action. Continued operation of the system in the Low range indicates inadequate waste treatment.
Meter Reading Salt Feed Valve Adjustment High Close Valve slightly Low Open valve slightly
If after about six normal uses the meter reading is still not in the Normal range, review the Start Up Procedures in Section IV. Also check Section VI, Troubleshooting.
D. SALT FEED ADJUSTMENTS The salt feed rate was originally set for dockside operation (Section IV, LECTRA/SAN START-UP), When sailing into waters that are significantly more or less saline, an adjustment of the salt feed valve should be made according to the following table:
Boat Movement Salt Feed Valve Adjustment To fresh water Open Valve To open sea To Open water Close Valve
E. SALT FEED TANK REFILLING PROCEDURES 1. Do not let the salt feed tank run dry. The toilet will not flush satisfactorily if the tank is dry and the head sucks in air. 2. Check level of brine in salt feed tank frequently. 3. Dissolve salt in a separate container and pour saturated solution into the salt feed tank, being careful no un-dissolved salt enters the tank which could clog components.
F. BOARDING AND DEPARTING PROCEDURES If the boat is not used for more than a two-day period, a treatment cycle should be routinely run prior to use. This is done with a clockwise turn of the knob on the Control Unit to activate LECTRA/SAN. The toilet is not flushed. When the boat is to be left for long periods, an extended flush and treatment cycle should be performed. Activate LECTRA/SAN with a clockwise turn of the knob on the Control Unit. Flush the toilet for about thirty (30) seconds or throughout the flush/pretreat cycle.
VI. TroubleShooting
Although LECTRA/SAN has been designed and engineered to be trouble-free, component or unit malfunction may cause the system to become inoperative or to operate incorrectly. A number of possible problems and their probable causes are listed below along with corrective action to be taken to remedy the problem. The corrective action steps should be performed in the order shown until the cause of the problem is corrected. Problem / Possible Cause
System Inoperative A. No power to Control Unit? A-1. Check for proper voltage (12,24, or 32 VDC) with volt meter between lugs D and E on the relay in the Control Unit (See Fig 6) If there is voltage go on to B. A-2. Check lug E to be sure it is properly tightened. Also check the power connection at the Treatment Unit and power supply. A-3. Check main power circuit breaker or fuse A-4. Check for dead battery or faulty converter B. Improper Wiring B-1. Check for proper wiring of Control Unit and Treatment Unit (See Figures 6 and 12) Be sure all connections are tight. C. Faulty Control Unit Timer C-l. Check for proper voltage (12,24, or 32 VDC) between terminal T-2 on the timer and terminal D on the relay. (See Fig. 6) If there is no voltage, recheck A above C-2. If there is proper voltage, check timer operation. Activate the timer with a clockwise turn of the knob and check for proper voltage (12,24, or 32 VDC) between terminal L-2 on the timer and terminal D on the relay. If there is no voltage the timer is faulty and must be replaced. C-3. Check for proper voltage (12, 24, or 32 VDC) between terminal T3 on the timer and terminal D on the relay during the treatment cycle if there is no voltage, timer is defective. Replace Timer. C-4. Check solenoid relay for continuity between terminals E & F after energizing D & G (see figure 12)
Flush/Pretreat Light Inoperative A. Fuse A blown A-1. Replace fuse A Be sure to check fuse specifications given in parts list on page 38. A-2. Check to see that connections on fuse clip are clean. Dirt and corrosion cause heat buildup which can result in a blown fuse. A-3. If replacement fuse A blows in the next operating cycle or soon after, the mixer (smaller) motor must be inspected for damage or excess loading on the shaft. Replace defective motor or clean shaft and impeller.
NOTE: See Specifications Section for proper amperages for motors & electrodes.
B. Defective LED Board B-1. Check all connections leading to the LED Board (Fig 12. page 41) to be sure terminals a, c, d are tight. B-2. Check for proper voltage (12,24, or 32 VDC) between Terminals (a) and (d) on the LED Board during the Flush/Pretreat cycle. If there is proper voltage and the Flush/Pretreat light does not operate then the LED Board is defective. Replace LED Board. B-3. If the proper voltage does not register between terminals (a) and (d) on the LED Board, check fuse A. If fuse is good, check timer.
|
|